BIRKAPILI HEPP

On November 24, 2000, ERE Hydroelectric Co. (previously ERE Autoproducer Co.) and the Ministry of Energy and Natural Resources signed the Autoproducer contract for Birkapili HEPP

Upon enactment of Energy Market Law No:4628, it is decided to establish the project under free electricity market conditions and a Generation Licence for 40 years was issued by EMRA on June 5th, 2003.

Upon completion of works, Preliminary Acceptance is signed on March 11th 2004 and Commercial Operation commenced.

The project, located in Icel Province in southern Turkiye, is expected to generate 177.6 GWh of electricity annually, with an installed power of 48.5 MW

Birkapili HEPP’s 1,010m Nominal Head is the highest in Turkey and also among world rankings.

birkapili_1

Birkapılı HES Cebri Borusu

First of the two primary schools being built by ERE in the project site, ERE – Dagpazari Primary School opened with the ceremony held on September 22nd, 2003. Our second school, ERE – Yapinti Primary School is also completed and opened for education on 2004-2005 semester.

Detailed information regarding the project is available at the following links;

BIRKAPILI HEPP Opening Ceremony, April 30th, 2004

Works of ‘Sogutozu & Dagpazari Regulators and Birkapili HEPP’ which had commenced on October-2001 were completed on March-2004 and plant had started commercial opertion, following the Preliminary Acceptance on March 11th, 2004.

Opening Ceremony of the plant is held on April 30th, 2004, with the kind participations of Minister of Energy Dr. Hilmi GULER, Energy Market Regulatory Authority Chairman Mr. Yusuf GUNAY and Mr. Korkut OZAL alongwith a strong interest from protocol, local public and guests.

We would like to present our sincere gratitude to all our guests who honoured our ceremony with their attendance.

Photographs from the Opening Ceremony

DAGPAZARI REGULATORS and
BIRKAPILI
HEPP GENERAL
TECHNICAL INFORMATION
Project Location Mut Province

– ICEL

REGULATOR I
Height Above

Foundation

3.10 m
Normal Water Level 1,434.50 m
Crest Length 7.50 m
Regulator Type Front Intake,

Concrete Mass

REGULATOR II
Height Above

Foundation

6.00 m
Normal Water Level 1,229.00 m
Crest Length 35.00 m
Regulator Type Front Intake

– with Spillway

POWER TUNNEL (1&2)
Type Basket Handle
Slope 0.0006
Length (1) 3,195.00 m
Length (2) 3,092.00 m
OPEN CHANNEL (1&2)
Type Rectangular
reinforced
concrete
Slope 0.0003
Length (1) 138.00 m
Length (2) 1 ,875.00 m
HEAD POND
Width 27.00 m
Length 50.00 m
Volume 8,100.00 m3
PENSTOCK
Type Welded Steel
Diameter 1.35 – 1.10 m
Length 3,482.69 m
Thickness 10 – 28 mm
POWER HOUSE
Width 19.90 m
Length 21.10 m
Height 28.20 m
TURBINE
Type Vertical

Axis Pelton

Design Flow 6.18 m3/s
Design Head 1,010.00 m
Unit Power 48.50 MW
No of Units 1 ad.
Installed Power 48.50 MW
GENERATOR
Type Vertical

Axis Pelton

Unit Power 53.44 MW
No of Units 1 ad.
Installed Power 53.44 MW
Current 11.0 + 2.5%kV
Efficiency 0.97
AVERAGE ANNUAL
POWER
PRODUCTION
177,600,000
kWh